Mecer 10KVA Online Smart UPS
- 50Hz/60Hz frequency converter mode
- 110-300 VAC voltage range
- ECO energy saving mode
- 20 x12V 9Ah batteries parallel kit compatible
- 0.99 input power factor
- 0.8 output power factor
- EPOE (mergency power off function)
- SNMP+USB+RS-232 multiple communications
Specifications and features | |
Product Code | ME-10000-WPTU |
CAPACITY | 10000 VA / 8000 W |
PHASE | Single phase with ground |
INPUT | |
Input Voltage Range | 110-300 VAC (Based on load at 50%); 176-300 VAC (Based on load at 100%) |
Nominal Voltage | 208/220/230/240 VAC |
Frequency Range | 46~54 Hz or 56~64 Hz |
Power Factor | >= 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Voltage Regulation | ± 1% |
Output Voltage | 208/220/230/240 VAC |
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 0.1 Hz |
Transfer Time : AC Mode to Battery Mode | Zero |
Transfer Time : Inverter to Bypass | Zero |
Transfer Time : Waveform (Batt. Mode) | Pure Sine Wave |
Current Crest Ratio | 3::1 |
Harmonic Distortion | <= 3% THD (Linear Load); <= 5% THD (Non-linear Load) |
Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz |
EFFICIENCY | |
Battery Mode | 0.91 |
AC Mode | 0.93 |
BATTERY | |
Long-run Model: Battery Type | Depending on the capacity of external batteries |
Long-run Model: Charging Current (max.) | 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries) |
Long-run Model: Charging Voltage | 273 VDC ± 1% (Based on 20pcs bateries) |
Long-run Model: Numbers | 16~20 (Adjustable) |
Standard Model: Battery Type | 12 V / 9Â Ah |
Standard Model: Charging Current (max.) | 1A/2A |
Standard Model: Charging Voltage | 218.4 VDC ± 1%, 273 VDC ± 1% |
Standard Model: Numbers | 16, 20 |
Standard Model: Typical Recharge Time | 9 hours recover to 90% capacity |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
ENVIRONMENT | |
Operating Humidity | 0~95% RH @ 0- 40°C (non-condensing) |
Noise Level | Less than 58dB @ 1 Meter |
PHYSICAL | |
Standard Model : Dimension, D x W x H (mm) | 442 x 190 x 688 |
Standard Model : Net Weight (kgs) | 66, 76 |
Long-run Model : Dimension, D x W x H (mm) | 442 x 190 x 318 |
Long-run Model : Net Weight (kgs) | 16 |
MANAGEMENT | |
Optional SNMP | Power management from SNMP manager and web browser |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
- Serial and USB standard with parallel kit 20 x12V 9Ah batteries
- True double-conversion online UPS
- Wide input voltage range (110-300 VAC)
- Input power factor correction 0.99
- Output Power Factor 0.8
- 50Hz/60Hz frequency converter mode
- Programmable power management outlets
- Emergency power off function (EPO)
- ECO mode operation for energy saving (ECO)
- Charger capacity expansion to 8A for long-run models
- SNMP USB RS-232 multiple communications
- Smart battery charger design for optimized battery performance
- Selectable output voltage via LCD panel
- Hot-swappable battery design (only available for ME-1000-GRU/ME-2000-GRU/ME-3000-GRU)